40mm & 60mm Proportional Regulator 2R210
3
Parameter Number 6 Set Output Signal
Step 1 2 3 4 5
Press
3-6 seconds
Until
Display
Reads
Flashing Decimal
Flashing Decimal
(Value 0, 1 or 2) Flashing
Description
Accesses
changeable
parameters.
Accesses
parameter no. 6.
Displays current
parameter value.
1 = m factory
default for P3H with
analog options
Edits parameter.
0 = digital
(NPN or PNP)
1 = analog 0..10V
2 = analog 4..20 mA
Accepts and saves
new parameter
setting.
Sequences to next
parameter.
or
Parameter Number 8 Adjust Span Analog Output Signal
Step 1 2 3 4 5
Press
3-6 seconds
Until
Display
Reads
Flashing Decimal
(For 2 bar versions
value = 92)
Flashing Decimal
(Value between
0 and 130) Flashing
Description
Accesses
changeable
parameters.
Accesses
parameter no. 8.
Displays current
parameter value. Edits parameter.
Accepts and saves
new parameter
setting and
implements the new
analog signal span.
Sequences to next
parameter.
or
or
Adjust Digital Display
If necessary, adjustments can be made to the digital display when using an external pressure sensor.
ParameterNumber9–AdjustDigitalDisplayValue(PressureCalibration)
Step 1 2 3 4 5
Press
3-6 seconds
Until Display
Reads
Flashing Decimal Flashing Decimal Flashing
Description
Accesses
changeable
parameters.
Accesses
parameter no. 9.
Displays current
digital display
Use up or down
arrows and accept
to adjust the
display value if
using an external
pressure sensor.
Accepts and saves
new parameter
setting.
Sequences to next
parameter.
or
or